The ECBS003 series photoelectric direct-reading remote water meter is designed to measure and record the total volume of potable water flowing through municipal water pipelines. The measured water consumption can be converted into digital signals and transmitted for remote data collection.
Through handheld data collectors or existing communication networks, the system enables remote meter reading, monitoring, and management, improving efficiency and accuracy in water usage management.
• Dry-dial structure design.
• Clear and easy-to-read dial with long-term readability.
• Photoelectric encoded passive direct-reading technology.
• Data output via RS485 bus or M-BUS bus.
• Non-contact sensing technology that does not affect meter performance.
• Low-power design, requiring power supply only during data reading.
• Can be integrated with a host management system to enable remote meter reading and data collection.
• High measurement accuracy, up to R200.
• Optional valve control function, allowing terminals to control water usage by opening or closing the valve.
| Maximum Permissible Error | ±5% (Q1–Q2); ±2% (Q2–Q4), in accordance with standard metering accuracy ranges |
| Communication Interface | M-BUS / RS485 |
| Communication Protocol | CJ/T188-2004 (Technical Specification for Data Transmission of Household Metering Instruments); DL/T645-1997; Modbus Protocol; or other protocols as agreed by both parties. |
| Wireless Interface | Not supported |
| Water Temperature (Cold Water Meter) | 0°C ~ 30°C |
| Water Temperature (Hot Water Meter) | 0°C ~ 90°C |
| Maximum Operating Pressure | ≤ 1 MPa |
| Applicable Pipe Diameter | DN50 ~ DN300 |
| Communication Baud Rate | 1200 / 2400 / 4800 / 9600 bps |
| Communication Distance | ≤ 300 m |
| Operating Current | M-BUS: 1.0–1.3 mA RS485: 0.6–0.8 mA |
| Operating Voltage | DC 36 V (M-BUS) DC 12–24 V (RS485) |
| Data Storage Duration | Unlimited |
| Electromechanical Conversion Error | ≤ ±1 minimum conversion scale value |
| Valve Control | Not supported |
| Wiring Method | M-BUS: Standard two-core bus cable connection, non-polar. RS485: Standard four-core cable connection, two cores for power supply and two cores for signal transmission. |
| Recommended Cable Type | M-BUS: RVSP 2 × 1.0 mm² shielded twisted pair cable RS485: RVSP 4 × 1.0 mm² shielded twisted pair cable |
| Installation Guidelines | • Install the meter horizontally (vertical meters must be installed vertically), with the dial facing upward and the arrow aligned with the water flow direction. • Flush the pipeline before installation to remove debris and prevent meter damage. • Install in a dry location with sufficient space for maintenance and replacement. • Installation inside a dedicated water meter box is recommended. • Install isolation valves before and after the meter to facilitate maintenance and system control. |