Air Quality Monitoring Display Panel for Parking Garage Ventilation Systems ECBH013

Description

The ECBH013 air quality monitoring display panel is designed for indoor environmental monitoring and parking garage ventilation management applications. Supporting real-time CO, CO₂, temperature, and humidity monitoring with LED status display, the panel provides alarm indication and ventilation fan linkage functions for commercial buildings, underground parking systems, and green building projects.

Features

Multi-Parameter Environmental Monitoring

Supports real-time monitoring of CO, CO₂, temperature, and humidity parameters.

LED Status Display

LED display interface provides clear on-site environmental status indication.

Automatic Alarm Function

Supports configurable alarm and recovery thresholds for CO, CO₂, temperature, and humidity monitoring.

Ventilation Fan Linkage

Automatically triggers ventilation fan control based on CO₂ concentration thresholds.

High-Performance Sensor Design

Uses high-quality electrochemical sensors with high accuracy, stability, and long service life.

Flame-Retardant Housing

High-quality flame-retardant PC housing designed for commercial building environments.

86 Box Compatible Installation

Compatible with standard 86 installation boxes for modern building applications.

Hidden Terminal Wiring

Rear terminal concealed wiring design allows installation without disassembling the housing.

Specifications

Technical Specifications

Display Type LED Display
Monitoring Parameters CO / CO₂ / Temperature / Humidity
Working Voltage DC24V
Output Signal Two-Wire Bus
Dimensions 97 × 97 × 26 mm
Installation Compatibility Standard 86 Box Compatible

Optional Features

Alarm Monitoring CO / CO₂ / Temperature / Humidity
Ventilation Fan Linkage Supported
Sensor Type Electrochemical Sensor
Housing Material Flame-Retardant PC Material
Wiring Method Rear Concealed Terminal Wiring
Green Building Standard Compliance Supported

Alarm Threshold Settings

Monitoring Item Alarm Threshold Recovery Threshold Description
CO 25ppm 15ppm Natural ventilation garage CO concentration should not exceed 30ppm
CO₂ 1000ppm 900ppm Ventilation fan starts at ≥1000ppm and stops 60 seconds after recovery
Temperature & Humidity 33°C / 80%RH or 35°C / 90%RH 32°C / 77%RH or 34°C / 87%RH DIP switch configurable alarm and recovery thresholds

Available Models

Model Configuration
ECBH013 Air Quality Monitoring Display Panel

 

 

 

underground garage monitoring system

System Architecture

Air Quality Monitoring Control Panel for Ventilation & Fire Safety Systems
View Our Solution
View Our Projects

Looking for pricing or more details on this product?

Can’t find what you’re looking for? Tell us your requirements.

Confident businesswoman using her tablet and phone, smiling outdoors in sunlight.

Tell us your requirements.

We’ll recommend the right monitoring solution.